Low Voltage Switchgear with Ccf Configuration for Jiangxi Power

Product Details
Customization: Available
Certification: CCC, ISO9001
Shell Material: Stainless Steel
Manufacturer/Factory & Trading Company

360° Virtual Tour

Diamond Member Since 2025

Suppliers with verified business licenses

Audited Supplier Audited Supplier

Audited by an independent third-party inspection agency

National Award received
This supplier had received national award, you can check the Audit Report for more information
Fast Delivery
The supplier can deliver the goods within 15 days
R&D Capabilities
The supplier has 4 R&D engineers, you can check the Audit Report for more information
Raw-Materials Traceability
The supplier has traceability identification of raw materials
to see all verified strength labels (24)
  • Low Voltage Switchgear with Ccf Configuration for Jiangxi Power
  • Low Voltage Switchgear with Ccf Configuration for Jiangxi Power
  • Low Voltage Switchgear with Ccf Configuration for Jiangxi Power
  • Low Voltage Switchgear with Ccf Configuration for Jiangxi Power
  • Low Voltage Switchgear with Ccf Configuration for Jiangxi Power
  • Low Voltage Switchgear with Ccf Configuration for Jiangxi Power
Find Similar Products

Basic Info.

Model NO.
PN-XGN12/24
Voltage Level
Medium Voltage
Installation
Fixed
Structure
Cabinet
Current
AC
Province
Jiangxi
Color
Custom
Configuration
Ccf
Rated Voltage
Rated Voltage
Protection Class
IP65
Rated Frequency
50Hz/60Hz
Transport Package
Wooden Packing
Specification
Custom
Trademark
Pino Electric
Origin
China
HS Code
85381010
Production Capacity
2000

Product Description

12kV XGN15 - 12 CCF Configuration Ring Main Unit: Meticulously Crafted for Precise Power Management

The XGN15 - 12 is available in a diverse array of configurations such as DF, CC, CCC, CCCC, FCC, CCF, CCCF, CCCCF, CF, CFC, CCFF, CCCFF, CFFC, CCVV, among others. In this detailed description, we will concentrate on the CCF configuration. However, each configuration is meticulously engineered to cater to varied requirements in power distribution systems, featuring different combinations of load break switch units, fuse-load break switch units, voltage transformer units, and other components. The 12kV XGN15 - 12 CCF configuration ring main unit is a premium electrical distribution solution that masterfully combines regular load switching with superior protection capabilities. Tailored to address the unique demands of power systems, this configuration provides a strategic blend of standard load control and pinpointed fault protection.

1. Design and Component Functionality

Load Break Switch Units (C)

The two "C" units within the CCF configuration are essential for managing normal load current switching. These load break switches are engineered with top-tier materials to guarantee dependable performance. The contacts, often crafted from silver-nickel alloys, ensure outstanding electrical conductivity and durability. Each "C" unit is designed to handle substantial load currents, typically up to the rated capacity of the ring main unit, ranging from 630A to 1250A, contingent upon the model.
 
Designed to manage the power flow to various electrical circuits or loads, these switches exemplify versatility. For instance, in a medium-sized industrial facility, one "C" unit might be allocated to energize the production line machinery, while the other governs the facility's lighting system. This segregation of loads ensures independent control, empowering operators to modulate power supply based on the precise demand of each circuit.

Fuse - Load Break Switch Combination Unit (F)

The "F" unit in the CCF configuration is a pivotal component that seamlessly integrates the functionalities of a load break switch and a fuse. This unit is expertly crafted to shield specific sections of the electrical system from over-currents and short-circuits. The fuse, a fast-acting device within the "F" unit, swiftly disrupts the circuit upon detecting abnormal currents.
 
The load break switch segment of the "F" unit also facilitates regular load current switching, offering capabilities to connect or disconnect electrical loads during routine operations akin to a conventional load break switch. This dual-functionality renders the "F" unit exemplary for safeguarding critical apparatus, such as transformers or high-value industrial machinery. For instance, in a data center, the "F" unit can defend the servers' power supply, ensuring that any electrical anomalies are promptly isolated, thereby preserving the servers from harm.

2. Robust Construction

Enclosure

The CCF configuration ring main unit is encased in a resilient and protective housing. Typically crafted from corrosion-resistant materials like galvanized steel or aluminum-coated steel, the enclosure adheres to specific IP (Ingress Protection) standards, generally ranging from IP3X to IP5X. An IP3X rating safeguards against solid objects larger than 2.5 mm, whereas IP5X offers advanced protection against dust penetration.
 
Equipped with apt ventilation to avert overheating during sustained operations, the enclosure also boasts a modular design, facilitating straightforward access to internal components for maintenance and repairs. This modularity empowers technicians with the ease of replacing faulty parts efficiently, thus minimizing downtime and maintenance expenses.

Mounting Structure

The unit boasts an exceptionally stable mounting structure, ensuring effortless and secure installation. Whether on walls, poles, or nestled within switchgear cabinets, its design is meticulously engineered to withstand both vibrations and mechanical stresses. This guarantees that the ring main unit remains steadfastly in place throughout operation. Such unwavering stability is vital for the optimal performance of load break switches, as well as the fuse-load break switch combination unit. Any displacement or misalignment could potentially compromise their electrical efficiency.

3. Electrical Performance

Rated Voltage and Current

With a commanding rated voltage of 12kV, the XGN15 - 12 CCF configuration stands as an ideal choice for medium-voltage power distribution systems. It is adept at accommodating normal electrical loads within its rated current capacity, thereby ensuring a consistent and stable power supply under typical operating conditions. Its remarkable capacity to handle varying load currents renders it highly adaptable, catering to a spectrum of electrical demands, from small-scale commercial equipment to medium-sized industrial machinery.

Protection and Switching Efficiency

Incorporating two load break switches alongside a fuse-load break switch, the CCF configuration delivers superior protection and unmatched switching efficiency. The fuse within the 'F' unit is engineered to respond with lightning speed to over-current and short-circuit faults, severing the current flow within milliseconds. The load break switches effortlessly manage standard load currents, with their robust design promising longevity, thereby ensuring reliable power distribution over extended periods.

4. Versatile Applications

Industrial Settings

Within industrial plants, the CCF configuration excels in focused power distribution management. Take, for instance, a chemical manufacturing facility: the dual 'C' units can energize distinct production processes, while the 'F' unit safeguards essential pumps and compressors, pivotal for the manufacturing cycle. This strategic setup allows for enhanced power distribution control and significantly diminishes the likelihood of equipment damage due to electrical anomalies.

Commercial Buildings

In commercial edifices such as hotels or expansive retail outlets, the CCF configuration is the epitome of efficient power management solutions. The 'C' units adeptly regulate power delivery across various building zones, including lobbies, guest rooms, or store aisles. Meanwhile, the 'F' unit serves as a guardian for the building's key electrical systems, like elevator control mechanisms or central HVAC units, ensuring their uninterrupted and safe functionality.
 
The 12kV XGN15 - 12 CCF configuration ring main unit emerges as a dependable and high-performance solution for diverse power distribution needs. Its distinctive blend of components establishes it as a valuable asset for systems demanding both routine load management and superior fault protection.
 
Technical Specification PN-XGN12/24 Switchgear
Rated voltage kV 12 24
Frequency Hz 50/60 50/60
Lightning impulse withstand voltage Phase to phase, phase to earth kV 75 125
Fracture kV 85 145
1 min Power frequency withstand voltage Phase to phase, phase to earth kV 42 65
Fracture kV 48 79
Rated frequency Hz 50/60 50/60
Rated current Main bus A 630 630
Branch bus A 630 630
Short time withstand current Main circuit kA 20/3S 20/3S
Earthing circuit kA 20/2S 20/2S
Rated withstand current (peak) kA 50 50
Rated transfering current A 1700 870
Protection level Ip2x
Load break switch mechanical life Times 2000 3000
Earthing switch mechanical life Times 2000 2000
 
Low Voltage Switchgear with Ccf Configuration for Jiangxi PowerLow Voltage Switchgear with Ccf Configuration for Jiangxi PowerLow Voltage Switchgear with Ccf Configuration for Jiangxi PowerLow Voltage Switchgear with Ccf Configuration for Jiangxi PowerLow Voltage Switchgear with Ccf Configuration for Jiangxi Power