High Performance DFW 10-12 Outdoor Cable Distribution Box for 10kV Power Systems
Our DFW 10 - 12 Outdoor Cable Distribution Box is an essential and high quality electrical device designed for seamless operation within 10kV power systems. It plays a crucial role in relay tapping and power distribution, making it a cornerstone for efficient outdoor cable management.
1. Versatile Design and Functionality
- Dual - Function Variants: This distribution box comes in two main types. The economical cable distribution box is cost effective, suitable for projects with budget conscious requirements. The distribution cable with switch cable type offers enhanced control and flexibility, allowing for easy switching operations and better management of power distribution.
- Sealing Options: It can be classified into ordinary and flood - type based on its sealing properties. The ordinary type is ideal for general outdoor environments, while the flood type is engineered to withstand challenging conditions, such as areas prone to waterlogging. This ensures the reliability and durability of the box in various terrains and weather conditions.
2. Wide - ranging Applications
- Urban and Industrial Settings: Widely utilized in urban areas and industrial and mining enterprises' concentrated zones. In cities, it is a key component in achieving the transformation of the city power grid to a cable based system. It enables efficient power distribution, ensuring a stable power supply for residential, commercial, and public facilities.
- Ring Network Power Supply: It is the preferred product for implementing ring network power supply systems. By facilitating the collection and tapping of outdoor cables, it contributes to the construction of a more reliable and resilient power grid, minimizing power outages and enhancing the overall quality of power supply.
3. Technical Specifications and Quality Assurance
- Power System Compatibility: Specifically designed for 10kV power systems, it meets all the relevant industry standards and regulations. Rigorous quality control measures are implemented during the manufacturing process to ensure high - performance operation and long - term reliability.
- Durable Construction: Made from high quality materials, the distribution box can withstand harsh outdoor environments, including extreme temperatures, humidity, and mechanical stress.
The DFW 10-12 Outdoor Cable Distribution Box is a reliable, versatile, and high performance solution for outdoor power distribution needs. It is an ideal choice for power grid projects aiming to enhance power supply stability and efficiency.
Technical Parameters
12kv Technical Parameter |
Unit |
C module |
F module |
V module |
CB module |
Load
break
switch |
Switch
fuse |
Vacuum
circuit
breaker |
Isolate/
earthing switch |
Vacuum
circuit
breaker |
Isolate/
earthing
switch |
Rated Voltage |
KV |
12 |
12 |
12 |
12 |
12 |
12 |
Rated Frequency |
HZ |
50 |
50 |
50 |
50 |
50 |
50 |
Power Frequence Withstand Voltage |
KV |
42 |
42 |
42 |
42 |
42 |
42 |
Impulse Withstand Voltage |
KV |
75/85 |
75/85 |
75/85 |
75/85 |
75/85 |
75/85 |
Rated Current |
A |
630 |
1250 |
630 |
630 |
|
|
Closed Loop |
A |
630 |
|
|
|
|
|
Off Load Cable Charging |
A |
10 |
|
|
|
|
|
Rated Active Load Drop-oput Current |
A |
630 |
630 |
|
|
|
|
When Earth Fault Frop out Current of Cable Charging |
A |
17.4 |
|
|
|
|
|
Short Circuit Drop-out Current |
KA |
|
31.5 |
25 |
|
|
|
Making Capacity |
KA |
50 |
note |
63 |
63 |
63 |
63 |
Rated Short Time Withstand Current |
KA/3S |
20 |
|
20 |
20 |
25 |
25 |
Transfer Current |
A |
|
1700 |
|
|
|
|
Loop Resistance |
μΩ |
≤300 |
≤600 |
|
|
|
|
Mechanical Life |
Times |
5000 |
5000 |
10000 |
3000 |
10000 |
3000 |
24kv Technical Parameter |
Unit |
C module |
F module |
V module |
CB module |
Load
break
switch |
Switch
fuse |
Vacuum
circuit
breaker |
Isolate/
earthing switch |
Vacuum
circuit
breaker |
Isolate/
earthing switch |
Rated Voltage |
KV |
24 |
24 |
24 |
24 |
24 |
24 |
Rated Frequency |
HZ |
50 |
50 |
50 |
50 |
50 |
50 |
Power Frequence Withstand Voltage |
KV |
65 |
65 |
65 |
65 |
65 |
65 |
Impulse Withstand Voltage |
KV |
125 |
125 |
125 |
125 |
125 |
125 |
Rated Current |
A |
630 |
125 |
630 |
|
|
|
Closed Loop |
A |
630 |
|
|
|
|
|
Off Load Cable Charging |
A |
10 |
|
|
|
|
|
Rated Active Load Drop-oput Current |
A |
31.5 |
630 |
|
|
|
|
When Earth Fault Frop out Current of Cable Charging |
A |
43.3 |
|
|
|
|
|
Short Circuit Drop-out Current |
KA |
|
|
20 |
20 |
25 |
|
Making Capacity |
KA |
50 |
|
50 |
50 |
63 |
63 |
Rated Short Time Withstand Current |
KA/3S |
20 |
|
16 |
16 |
20 |
20 |
Transfer Current |
A |
|
1400 |
|
|
|
|
Loop Resistance |
μΩ |
≤300 |
≤600 |
|
|
|
|
Mechanical Life |
Times |
5000 |
5000 |
10000 |
10000 |
10000 |
5000 |