Customization: | Available |
---|---|
Breaking Capacity: | 25ka |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
We always regard customer satisfaction as our pursuit goal. Adhering to the business philosophy of honesty, cooperation and value creation, our company has become an all-round high-level professional supplier of 24kv Solid Insulated Switchgear, Voltage Dry Type Transformer, Outdoor Electrical Circuit Breaker Panel Box. The most recent kinds are a great deal better than the preceding one particular and they are quite popular with lots of prospects. We earnestly carry out the contract, and we are a creditable enterprise with good market reputation and honest management.
Ambient conditions for usage
2.1 Ambient air temperature , upper limit: +40ºC, down limit: - 40ºC;
2.2 Above seal level: no higher than 2000m;
2.3 Air pressure: no higher than 700Pa (equal to wind speed 34m/s);
2.4 Thickness of covering ice 10mm;
2.5 Air polluted degree IV class;
2.6 Seism intensity grade is no high than 8;
2.7 Place where no inflammable, explosive, intensive chemic erosive material (like acid, alkali, smother) or intensive vibration.
Main Technical Data
3.1 Rated data of switch body see table 1.
Table1
No |
Name |
Unit |
Data |
||
1 |
Rated voltage |
kV |
40.5 |
||
2 |
Rated insulation level(sea level 2000m) |
1 1 minute P.F withstand voltage |
Dry test |
95 |
|
Wet test(insulated to ground) |
85 |
||||
Lightning impulse voltage(peek value)1.2/50μs |
185 |
||||
3 |
Rated current |
A |
1250,1600,2000,2500 |
||
4 |
Rated frequency |
Hz |
50/60 |
||
5 |
Rated short-circuit breaking current |
kA |
20,25,31.5 |
||
6 |
Rated operating sequence |
O-0.3s-CO-180s-C |
|||
7 |
Breaking times of rated short-circuit breaking current |
times |
20 |
||
8 |
Rated short-circuit closing current(peak) |
kA |
50,63,80 |
||
9 |
Rated peak withstand current |
50,63,80 |
|||
10 |
Rated short time withstand current |
20,25,31.5 |
Continue- table1
11 |
full breaking time |
s |
<0.125 |
12 |
rated short-circuit duration time |
4 |
|
13 |
mechanical life |
times |
10000 |
14 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
220 |
Mechanical features data of switch body see table 2.
Table2
No |
Item |
Unit |
Data |
1 |
Opening distance between contacts |
mm |
20±2 |
2 |
over travel of contact |
3±1 |
|
3 |
Average breaking speed |
m/s |
1.8±0.3 |
4 |
average closing speed |
0.8±0.3 |
|
5 |
Jumping time of contacts closing |
ms |
≤5 |
6 |
Three phase opening simultaneity |
≤2 |
|
7 |
Closing time |
40 ~ 100 |
|
8 |
Breaking time |
20 ~ 60 |
|
9 |
DC resistance of phase circuit per pole |
μΩ |
≤200 |
10 |
center distance between poles |
mm |
700±5 |
11 |
Fixed & moving contact erosion limit |
3 |
|
12 |
Rated spring tress of cotact in closing |
N |
3200±300 |
Main technical data of controller see table 3.
Table 3
No |
Item |
Data |
1 |
Input CT ratio |
/5A or /1A(according to end users) |
2 |
Rated voltage and frequency |
AC 220V/50Hz or AC 110V/50Hz |
3 |
Open & close operation power source |
DC 24V or AC 220V |
4 |
Output capacity |
No less than 600W |
5 |
Over current settings |
20%~300% continuous adjustable |
6 |
Quick break fixed value |
20%~1000% continuous adjustable |
7 |
Re-closing time |
0.1~600s continuous adjustable |
8 |
Delay time |
0.1~600s continuous adjustable |
9 |
Zero-sequence current |
10%~100% continuous adjustable |
10 |
Local remote controlling distance |
No less than 30m |
11 |
Remote controlling distance at far |
No less than 1200m |
12 |
Surroundings temperature |
-40ºC~50ºC |
As a qualified supplier, we have the ability to provide you with the best and most suitable products. If you do not meet the requirements, you can return or exchange the Heat Resistance Meter Box SMC/DMC Polyester Outdoor Power Enclosure until you are satisfied. To establish a deep impression of 'being honest and abiding by promises' in the eyes of customers is our unremitting pursuit. Pay attention to the communication with customers and continuous innovation is the consensus of all our staff. Since the establishment of our company, it is due to the continuous support and care of friends, as well as the hard work and dedication of all colleagues of the company, so that our company can continue to develop and thrive.